FEATURES - This handy type clamp tester has the biggest CT window in the world (108mmx128mm) and can measure AC load current (0.01A -3000A) just by clamping the conductor without disconnecting the circuit.
| SPECIFICATIONS |
|---|
| Measuring function | : | AC load current |
|---|
| Safety standard | : | IEC61010-1, IEC61010-2-032 Installation Category. CategoryⅢ600V |
|---|
| Max Jaw Opening capability | : | 108mm (108x128mm) |
|---|
| Measuring range | : | AC30A/300A/3000A (50/60Hz) 3 ranges manual |
|---|
| Accuracy | : | 23℃±5℃ 80%RH or less (50/60Hz) | Range | Resolution | Accuracy(50/60Hz) |
|---|
| AC 30A | 0.01A | ±1.5%rdg±8dgt | | AC 300A | 0.1A | | AC 3000A | 1A | ±2.0%rdg±8dgt |
|
|---|
| Measuring method | : | Dual slope integration mode |
|---|
| AC conversion | : | AC coupled true rms responding |
|---|
| Display | : | LCD, max. 3200 count with annunciators |
|---|
| Over range indication | : | "OL" mark on LCD |
|---|
| Low battery indication | : | "Battery" mark on LCD |
|---|
| Data hold indication | : | "DH" mark on LCD |
|---|
| Sampling | : | 2 times/sec |
|---|
| Auto power off function | : | The meter is set to power off Approx. 10 minute later after power on. |
|---|
| Limitation of circuit voltage | : | Less than AC 600V |
|---|
| Withstanding voltage | : | AC 5500V, 1 minute (between operation handle and core of CT) |
|---|
| Operating temperature | : | 0℃ - 40℃, less than 80%RH (Without condensation) |
|---|
| Storage temperature | : | -10℃ - 60℃, less than 70%RH (Without condensation) |
|---|
| Power supply | : | 1.5V battery[UM-4 or AAA size]x 2 |
|---|
| Power consumption | : | Approx. 6mW |
|---|
| Battery life | : | Approx. 200 hours continuous |
|---|
| Dimension and weight | : | 194(W) x 341.5(H) x 52(D) mm, Approx. 1.8kgs |
|---|
| Accessories | : | | Battery (UM-4) | : | 2 | | Instruction Manual | : | 1 | | Carrying Case | : | 1 | | Hand Strap | : | 1 |
|
|---|
|