| SPECIFICATIONS | |
|---|---|
| Measuring function | AC leakage current and AC load current | 
| Display | LCD max.3200 count with annunciators | 
| Range | AC 3000mA/30A/300A/3000A(50Hz/60Hz) | 
| Range selector | 4 range manual by rotary switch | 
| Measuring sensor | Flexible current sensor | 
| Inside diameter of sensor | φ210mm | 
| A/D Conversion | Dual slope integration method | 
| Filter function | By filter switch (Low pass filter:150Hz) | 
| Over range indication | "OL" mark on LCD | 
| Data hold indication | "DH" mark on LCD | 
| Low battery indication | "Battery" mark on LCD | 
| Auto power off | Approx. 10 minutes after power on (Auto power off function can be released by the connection of recorder)  | 
| Sampling rate | 2 time/sec. | 
| Analog signal output | DC 300mV full scale to each range(±2%F.S.) (Output impedance: less than 10kΩ)  | 
| Withstanding Voltage | AC 2200V/1 minute between flexible sensor and outer case | 
| Limitation of circuit voltage | Less than AC 600V | 
| Operating Temperature | 0~45℃, < 80%RH (without condensation) | 
| Storage Temperature | -10~60℃, < 70%RH (without condensation) | 
| Power supply | LR6, AM-3 or AA size battery×6 | 
| Size | Main unit:159(W)×105(H)×53(D)mm Flexible current sensor:Approx.650mm length with 2m lead  | 
| Accessories | Carrying case, Batteries, Instruction manual | 
| Option | Cable for recorder | 
 